42 • Fieldbus coupler / controller

Fieldbus coupler 750-333

3.1.8.1.42 DO I/O modules

Module

Identification

Identification

 

hex

dec

750-501, 750-502, 750-509, 750-512, 750-513,

0x20

32

750-514, 750-517

 

 

*750-501, *750-502, *750-509, *750-512, *750-513,

0x00

0

*750-514, *750-517

 

 

 

Parameter

 

 

 

 

Value

 

 

 

 

Meaning

 

I/O module is physically

 

 

plug fitted*)

 

 

The I/O module process data is:

 

 

 

 

 

 

 

 

 

- supplied to the I/O module

 

 

 

 

 

 

 

not plug fitted

 

 

- ignored by the coupler

 

Substitute channel x

 

 

 

0*)

 

 

 

 

If, in the case of a PROFIBUS-DP fault, the

 

 

 

 

 

 

 

 

 

 

 

switching of substitute values is enabled by the

 

 

 

 

 

 

 

1

 

 

 

 

 

bus coupler parameterisation, this data is trans-

 

 

 

 

 

 

 

 

 

 

 

 

 

mitted to the periphery in the case of a fault.

 

 

 

 

 

 

 

*) Default settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

Offset

Information

 

 

 

 

 

 

 

 

 

 

 

 

0

7

6

5

 

4

 

3

2

 

1

0

 

 

 

 

0

0

Plug

0

 

0

0

 

0

0

 

 

 

1

7

6

5

 

4

 

3

2

 

1

0

 

 

 

 

0

0

0

 

0

 

0

0

 

1

0

 

 

 

2

7

6

5

 

4

 

3

2

 

1

0

 

 

 

 

0

0

0

 

0

 

0

0

 

SV1

SV0

 

Plug5

 

0

 

Module is physically not present

 

 

 

SV00

 

1

 

Module is physically present (default)

 

 

 

Substitute value for channel 1

 

 

 

SV01

 

 

 

Substitute value for channel 2

 

 

 

Italic

 

 

 

Cannot be changed

 

 

 

 

D R A F T

WAGO-I/O-SYSTEM 750

2001-02-27

PROFIBUS

Fieldbus coupler / controller

• 43

Fieldbus coupler 750-333

 

 

 

3.1.8.1.52 DO I/O modules with 1 bit diagn. per channel

 

Module

 

 

 

 

 

 

 

 

 

 

Identification

Identification

 

 

 

 

 

 

 

 

 

 

 

 

 

hex

dec

 

750-507, 750-522

 

 

 

 

 

 

 

 

0x20

32

 

*750-507, *750-522

 

 

 

 

 

 

 

 

0x00

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

Value

 

 

 

 

Meaning

 

 

I/O module is physically

 

plug fitted*)

 

 

The I/O module process data is:

 

 

 

 

 

 

 

 

 

- supplied to the I/O module

 

 

 

 

 

 

 

not plug fitted

 

 

- ignored by the coupler

 

 

Diagnosis channel x

 

 

 

 

 

 

 

 

The diagnosis information of the corresponding

 

 

 

 

 

 

 

released*)

 

 

 

 

channel is

 

 

 

 

 

 

 

 

 

 

 

 

- transmitted to PROFIBUS-DP master

 

 

 

 

 

 

 

locked

 

 

 

 

- not transmitted to PROFIBUS-DP master

 

Substitute channel x

 

 

0*)

 

 

 

 

If, in the case of a PROFIBUS-DP fault, the

 

 

 

 

 

 

 

 

 

 

 

switching of substitute values is enabled by the

 

 

 

 

 

 

 

1

 

 

 

 

 

bus coupler parameterisation, this data is trans-

 

 

 

 

 

 

 

 

 

 

 

 

 

mitted to the periphery in the case of a fault.

 

 

 

 

 

 

 

*) Default settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

Offset

 

Information

 

 

 

 

 

 

 

 

 

 

 

 

0

 

7

6

5

4

 

3

2

 

1

0

 

 

 

 

 

 

0

0

Plug

0

 

Diag

Diag

 

0

0

 

 

 

 

 

 

 

 

 

 

 

En1

En0

 

 

 

 

 

 

 

1

 

7

6

5

4

 

3

2

 

1

0

 

 

 

 

 

 

0

0

0

0

 

0

0

 

1

1

 

 

 

 

2

 

7

6

5

4

 

3

2

 

1

0

 

 

 

 

 

 

0

0

0

0

 

0

0

 

SV1

SV0

 

 

Plug5

 

0

Module is physically not present

 

 

 

 

1Module is physically present (default)

DiagEn02

Diagnosis idle run, overload, short circuit on channel 1

0

lock

1

release

DiagEn13

Diagnosis idle run, overload, short circuit on channel 2

0

locked

1

released

SV00

Substitute value for channel 1

SV01

Substitute value for channel 2

Italic

Cannot be changed

WAGO-I/O-SYSTEM 750

D R A F T

PROFIBUS

2001-02-27

44 • Fieldbus coupler / controller

Fieldbus coupler 750-333

3.1.8.1.62 DO I/O module with 2 bit diagn. per channel

 

Module

 

 

 

 

 

 

 

 

 

 

Information

Information

 

 

 

 

 

 

 

 

 

 

 

 

 

hex

dec

 

750-506

 

 

 

 

 

 

 

 

 

 

0x20

32

 

*750-506

 

 

 

 

 

 

 

 

 

0x00

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

Value

 

 

 

 

Meaning

 

 

I/O module is physically

 

plug fitted*)

 

 

The I/O module process data is:

 

 

 

 

 

 

 

 

 

- supplied to the I/O module

 

 

 

 

 

 

 

not plug fitted

 

 

- ignored by the coupler

 

 

Diagnosis channel x

 

 

 

 

 

 

 

 

The diagnosis information of the corresponding

 

 

 

 

 

 

 

released*)

 

 

 

 

channel is

 

 

 

 

 

 

 

 

 

 

 

 

- transmitted to PROFIBUS-DP master

 

 

 

 

 

 

 

locked

 

 

 

 

- not transmitted to PROFIBUS-DP master

 

Substitute channel x

 

 

0*)

 

 

 

 

If, in the case of a PROFIBUS-DP fault, the

 

 

 

 

 

 

 

 

 

 

 

switching of substitute values is enabled by the

 

 

 

 

 

 

 

1

 

 

 

 

 

bus coupler parameterisation, this data is trans-

 

 

 

 

 

 

 

 

 

 

 

 

 

mitted to the periphery in the case of a fault.

 

 

 

 

 

 

 

*) Default settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

Offset

 

Information

 

 

 

 

 

 

 

 

 

 

 

 

0

 

7

6

5

4

 

3

2

 

1

0

 

 

 

 

 

 

0

0

Plug

0

 

Diag

Diag

 

0

1

 

 

 

 

 

 

 

 

 

 

 

En1

En0

 

 

 

 

 

 

 

1

 

7

6

5

4

 

3

2

 

1

0

 

 

 

 

 

 

0

0

0

0

 

0

0

 

1

1

 

 

 

 

2

 

7

6

5

4

 

3

2

 

1

0

 

 

 

 

 

 

0

0

0

0

 

0

0

 

SV1

SV0

 

 

Plug5

 

0

Module is physically not present

 

 

 

 

1Module is physically present (default)

DiagEn02

Diagnosis idle run, short circuit, lower voltage on channel 1

0

locked

1

released

DiagEn13

Diagnosis idle run, short circuit, lower voltage on channel 2

0

locked

1

released

SV00

Substitute value for channel 1

SV01

Substitute value for channel 2

Italic

cannot be changed

D R A F T

WAGO-I/O-SYSTEM 750

2001-02-27

PROFIBUS

Fieldbus coupler / controller

• 45

Fieldbus coupler 750-333

 

 

 

3.1.8.1.74 DO I/O modules

 

Module

 

 

 

 

 

 

 

 

 

 

Identification

Identification

 

 

 

 

 

 

 

 

 

 

 

 

 

hex

dec

 

750-504, 750-516, 750-519

 

 

 

 

 

 

 

0x20

32

 

*750-504, *750-516, *750-519

 

 

 

 

 

 

0x00

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

Value

 

 

 

 

Meaning

 

 

I/O module is physically

 

plug fitted*)

 

 

The I/O module process data is:

 

 

 

 

 

 

 

 

 

- supplied by the I/O module

 

 

 

 

 

 

 

not plug fitted

 

 

- ignored by the coupler

 

 

Substitute channel x

 

 

0*)

 

 

 

 

If, in the case of a PROFIBUS-DP fault, the

 

 

 

 

 

 

 

 

 

 

 

switching of substitute values is enabled by the

 

 

 

 

 

 

 

1

 

 

 

 

 

bus coupler parameterisation, this data is trans-

 

 

 

 

 

 

 

 

 

 

 

 

 

mitted to the periphery in the case of a fault.

 

 

 

 

 

 

 

*) Default settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

Offset

 

Information

 

 

 

 

 

 

 

 

 

 

 

 

0

 

7

6

5

4

 

3

2

 

1

0

 

 

 

 

 

 

0

0

Plug

0

 

0

0

 

0

1

 

 

 

 

1

 

7

6

5

4

 

3

2

 

1

0

 

 

 

 

 

 

0

0

0

0

 

0

0

 

1

0

 

 

 

 

2

 

7

6

5

4

 

3

2

 

1

0

 

 

 

 

 

 

0

0

0

0

 

SV3

SV2

 

SV1

SV0

 

 

Plug5

 

0

Module is physically not present

 

 

 

 

1Module is physically present (default)

SV00

Substitute value for channel 1

SV01

Substitute value for channel 2

SV02

Substitute value for channel 3

SV03

Substitute value for channel 4

Italic

Cannot be changed

WAGO-I/O-SYSTEM 750

D R A F T

PROFIBUS

2001-02-27

46 • Fieldbus coupler / controller

Fieldbus coupler 750-333

3.1.8.1.82 DI/DO I/O module with 1 bit diagn. per channel

 

Module

 

 

 

 

 

 

 

 

 

 

Identification

Identification

 

 

 

 

 

 

 

 

 

 

 

 

 

hex

dec

 

750-418

 

 

 

 

 

 

 

 

 

 

0x30

48

 

*750-418

 

 

 

 

 

 

 

 

 

0x00

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

Value

 

 

 

 

Meaning

 

 

I/O module is physically

 

plug fitted*)

 

 

The I/O module process data is:

 

 

 

 

 

 

 

 

 

- supplied to the I/O module

 

 

 

 

 

 

 

not plug fitted

 

 

- ignored by the coupler

 

 

Diagnosis channel x

 

 

 

 

 

 

 

 

The diagnosis information of the corresponding

 

 

 

 

 

 

 

released*)

 

 

 

 

channel is

 

 

 

 

 

 

 

 

 

 

 

 

- transmitted to PROFIBUS-DP master

 

 

 

 

 

 

 

locked

 

 

 

 

- not transmitted to PROFIBUS-DP master

 

 

 

 

 

 

 

*) Default settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

Offset

 

Information

 

 

 

 

 

 

 

 

 

 

 

 

0

 

7

6

5

4

 

3

2

 

1

0

 

 

 

 

 

 

0

0

Plug

0

 

Diag

Diag

 

0

1

 

 

 

 

 

 

 

 

 

 

 

En1

En0

 

 

 

 

 

 

 

1

 

7

6

5

4

 

3

2

 

1

0

 

 

 

 

 

 

0

0

0

0

 

0

1

 

1

1

 

 

 

 

2

 

7

6

5

4

 

3

2

 

1

0

 

 

 

 

 

 

0

0

0

0

 

0

0

 

0

0

 

 

 

Plug5

 

0

Module is physically not present

 

 

 

 

1Module is physically present (default)

DiagEn02

Diagnosis idle run, overload, short circuit on channel 1

0

lock

1

release

DiagEn13

Diagnosis idle run, overload, short circuit on channel 2

0

locked

1

released

Italic

Cannot be changed

D R A F T

WAGO-I/O-SYSTEM 750

2001-02-27

PROFIBUS