Fieldbus coupler / controller • 107

Fieldbus Controller 750-833

3.2.8.2.24 AI module

 

Module

 

 

 

 

 

 

 

 

 

 

 

Identification

Identification

 

 

 

 

 

 

 

 

 

 

 

 

 

 

hex

dec

 

750-468

 

 

 

 

 

 

 

 

 

 

 

0x53

83

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

 

Value

 

 

 

 

Meaning

 

 

I/O module is physically

 

 

plug fitted*)

 

 

The I/O module process data is:

 

 

 

 

 

 

 

 

 

 

- supplied by the I/O module

 

 

 

 

 

 

 

 

not plug fitted

 

 

- set to zero by the controller

 

Diagnosis channel x

 

 

 

 

 

 

 

 

 

The diagnosis information of the corresponding

 

 

 

 

 

 

 

 

released*)

 

 

 

 

channel is

 

 

 

 

 

 

 

 

 

 

 

 

 

- transmitted to PROFIBUS-DP master

 

 

 

 

 

 

 

 

locked

 

 

 

 

- not transmitted to PROFIBUS-DP master

 

 

 

 

 

 

 

 

*) Default settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Offset

 

Information

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

7

6

5

 

4

 

3

2

 

1

0

 

 

 

 

 

 

0

PFC

Plug

 

0

 

Diag

Diag

 

0

0

 

 

 

 

 

 

 

 

 

 

 

 

En1

En0

 

 

 

 

 

 

 

1

 

7

6

5

 

4

 

3

2

 

1

0

 

 

 

 

 

 

reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

15

14

13

 

12

 

11

10

 

9

8

 

 

 

 

 

 

reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

7

6

5

 

4

 

3

2

 

1

0

 

 

 

 

 

 

reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

PFC6

 

0

 

Module is mapped in the fieldbus and PFC-PI

 

Plug5

 

1

 

Module is exclusively mapped in the PFC-PI

 

 

0

 

Module is physically not present

 

DiagEn02

 

1

 

Module is physically present (default)

 

 

0

 

Lock diagnosis channel 1

 

 

 

 

DiagEn13

 

1

 

Diagnosis channel 1 released

 

 

 

 

 

0

 

Diagnosis channel 2 locked

 

 

 

 

Italic

 

1

 

Diagnosis channel 2 released

 

 

 

 

 

 

 

Cannot be changed

 

 

 

 

 

WAGO-I/O-SYSTEM 750

D R A F T

PROFIBUS

2001-02-27

108 • Fieldbus coupler / controller

Fieldbus Controller 750-833

3.2.8.2.32 AO modules

All analog output modules have 6 bytes of extended parameterised information and offer the possibility to switch to parameterisable substitute values in case of a master failure.

 

Module

 

 

 

 

 

 

 

 

 

 

 

 

Identification

 

Identification

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

hex

 

dec

 

750-550, 750-552, 750-554, 750-556

 

 

 

 

 

 

0x61

 

97

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

 

Value

 

 

 

 

 

Meaning

 

 

I/O module is physically

 

 

 

 

 

 

 

 

The I/O module process data is:

 

 

 

 

 

 

 

 

Plug fitted*)

 

 

 

- supplied by the I/O module

 

 

 

 

 

 

 

 

Not plug fitted

 

 

 

- ignored by the controller

 

 

Diagnosis channel x

 

 

 

 

 

 

 

 

 

 

The diagnosis information of the corresponding

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

channel is

 

 

 

 

 

 

 

 

 

Released

 

 

 

 

 

- transmitted to PROFIBUS-DP master

 

 

 

 

 

 

 

 

Locked*)

 

 

 

 

 

- not transmitted to PROFIBUS-DP master

 

Substitute value channel x

 

0x0000 or 0x8000

 

If, in the case of a PROFIBUS-DP fault, the

 

 

 

 

 

 

 

 

 

switching of substitute values is enabled by the

 

 

 

 

 

 

 

 

0 or -32767

 

 

 

bus controller parameterisation, this data is

 

 

 

 

 

 

 

 

... 0x7FFF

 

 

 

transmitted to the periphery in the case of a

 

 

 

 

 

 

 

 

...

32767

 

 

 

 

 

fault.

 

 

 

 

 

 

 

 

 

*) Default setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Offset

 

Information

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

7

6

 

5

4

 

3

2

 

1

 

0

 

 

 

 

 

 

 

0

PFC

 

Plug

0

 

0

0

 

0

 

0

 

 

 

 

 

1

 

7

6

 

5

4

 

3

2

 

1

 

0

 

 

 

 

 

 

 

reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

15

14

 

13

12

 

11

9

 

8

 

7

 

 

 

 

 

 

 

SubVal

_Ch1_HB

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

7

6

 

5

4

 

3

2

 

1

 

0

 

 

 

 

 

 

 

SubVal

_Ch1_LB

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

15

14

 

13

12

 

11

10

 

9

 

8

 

 

 

 

 

 

 

SubVal

_Ch2_HB

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

7

6

 

5

4

 

3

2

 

1

 

0

 

 

 

 

 

 

 

SubVal

_Ch2_LB

 

 

 

 

 

 

 

 

 

 

 

 

PFC6

 

0

 

Module is mapped in the fieldbus and PFC-PI

 

Plug5

 

1

 

Module is exclusively mapped in the PFC-PI

 

 

 

0

 

Module is physically not present

 

 

 

 

 

 

1

 

Module is physically present (default)

 

SubVal_Ch1

 

0x0000

Substitute value channel 1

 

 

 

 

 

 

 

 

 

 

:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0xFFFF

 

 

 

 

 

 

 

 

 

 

 

 

SubVal_Ch2

 

0x0000

Substitute value channel 2

 

 

 

 

 

 

 

 

 

 

:

 

 

 

 

 

 

 

 

 

 

 

 

 

Italic

 

 

0xFFFF

Cannot be changed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D R A F T

WAGO-I/O-SYSTEM 750

2001-02-27

PROFIBUS

Fieldbus coupler / controller • 109

Fieldbus Controller 750-833

3.2.8.3Special digital modules

All special digital modules have 2 bytes of extended parameterisation information which serves for the identification on internal bus and the structure of the mapping table.

Input modules (counter) are followed by 2 bytes which are reserved for future options.

For output modules (PWM outputs) are followed by 6 byte of parameterisation data which serve for the saving of substitute values for a maximum of 2 channels (2 words).

3.2.8.3.1Counter modules

 

Module

 

 

 

 

 

 

 

 

 

 

Identification

Identification

 

 

 

 

 

 

 

 

 

 

 

 

 

hex

dec

 

750-404, 750-638

 

 

 

 

 

 

 

 

0xF2

242

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

Value

 

 

 

 

Meaning

 

 

I/O module is physically

 

 

 

 

 

 

 

The I/O module process data is:

 

 

 

 

 

 

 

plug fitted*)

 

 

- supplied by the I/O module

 

 

 

 

 

 

 

not plug fitted

 

 

- set to zero by the controller

 

 

 

 

 

 

 

*) Default setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

Offset

 

Information

 

 

 

 

 

 

 

 

 

 

 

 

0

 

7

6

5

4

 

3

2

 

1

0

 

 

 

 

 

 

0

PFC

Plug

0

 

0

0

 

0

0

 

 

 

 

1

 

7

6

5

4

 

3

2

 

1

0

 

 

 

 

 

 

reserved

 

 

 

 

 

 

 

 

 

 

 

 

2

 

15

14

13

12

 

11

9

 

8

7

 

 

 

 

 

 

reserved

 

 

 

 

 

 

 

 

 

 

 

 

3

 

7

6

5

4

 

3

2

 

1

0

 

 

 

 

 

 

reserved

 

 

 

 

 

 

 

 

 

 

 

PFC6

 

0

 

 

Module is mapped in the fieldbus and PFC-PI

 

Plug5

 

1

 

 

Module is exclusively mapped in the PFC-PI

 

 

0

 

 

Module is physically not present

 

Italic

 

1

 

 

Module is physically present (default)

 

 

 

 

 

Cannot be changed

 

 

 

 

 

WAGO-I/O-SYSTEM 750

D R A F T

PROFIBUS

2001-02-27

110 • Fieldbus coupler / controller

Fieldbus Controller 750-833

3.2.8.3.2PWM module

 

Module

 

 

 

 

 

 

 

 

 

 

 

 

 

Identification

Identification

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

hex

dec

 

750-511

 

 

 

 

 

 

 

 

 

 

 

 

 

0xF2

242

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

 

Wert

 

 

 

 

 

Meaning

 

 

I/O module is physically

 

 

 

 

 

 

 

 

 

The I/O module process data is:

 

 

 

 

 

 

 

 

plug fitted*)

 

 

 

- supplied by the I/O module or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

supplied to the I/O module

 

 

 

 

 

 

 

 

not plug fitted

 

 

 

- set to zero by the controller or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ignored by controller

 

 

Substitute value channel x

 

0x0000 *)

 

 

 

 

 

If, in the case of a PROFIBUS-DP fault, the

 

 

 

 

 

 

 

 

 

 

 

 

 

switching of substitute values is enabled by the

 

 

 

 

 

 

 

 

... 0x7FFF

 

 

 

bus controller parameterisation, this data is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

transmitted to the periphery in the case of a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

fault.

 

 

 

 

 

 

 

 

 

*) Default setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Offset

 

Information

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

7

6

 

5

4

 

3

 

2

 

1

 

0

 

 

 

 

 

 

0

PFC

 

Plug

0

 

0

 

0

 

0

 

0

 

 

 

 

1

 

7

6

 

5

4

 

3

 

2

 

1

 

0

 

 

 

 

 

 

1

0

 

1

1

 

1

 

1

 

0

 

1

 

 

 

 

2

 

15

14

 

13

12

 

11

 

9

 

8

 

7

 

 

 

 

 

 

reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

7

6

 

5

4

 

3

 

2

 

1

 

0

 

 

 

 

 

 

0

0

 

0

0

 

0

 

0

 

0

 

0

 

 

 

 

4

 

15

14

 

13

12

 

11

 

9

 

8

 

7

 

 

 

 

 

 

SubVal

_Ch1_HB

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

7

6

 

5

4

 

3

 

2

 

1

 

0

 

 

 

 

 

 

SubVal_Ch1_LB

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

15

14

 

13

12

 

11

 

10

 

9

 

8

 

 

 

 

 

 

SubVal

_Ch2_HB

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

7

6

 

5

4

 

3

 

2

 

1

 

0

 

 

 

 

 

 

SubVal

_Ch2_LB

 

 

 

 

 

 

 

 

 

 

 

 

Plug5

 

 

0

 

 

Module is physically not present

 

 

 

 

 

 

1

 

 

Module is physically present (default)

 

SubVal_Ch1

 

0x0000

 

Substitute value channel 1

 

 

 

 

 

 

 

 

 

:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0xFFFF

 

 

 

 

 

 

 

 

 

 

 

 

SubVal_Ch2

 

0x0000

 

Substitute value channel 2

 

 

 

 

 

 

 

 

 

:

 

 

 

 

 

 

 

 

 

 

 

 

 

Italic

 

 

0xFFFF

 

Cannot be changed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D R A F T

WAGO-I/O-SYSTEM 750

2001-02-27

PROFIBUS

Fieldbus coupler / controller • 111

Fieldbus Controller 750-833

3.2.8.4Distance and Angle Messurment Modules

All interface modules for path and angle measurement have 2 bytes of extended parameterisation information which serves for the identification on internal bus and the structure of the mapping table. 2 further bytes follow which are reserved for future options.

3.2.8.4.1SSI generator interface

 

Module

 

 

 

 

 

 

 

 

 

Identification

Identification

 

 

 

 

 

 

 

 

 

 

 

 

hex

dec

 

750-630 (Alternative)

 

 

 

 

 

 

 

0x93

147

 

750-630 (Standard)

 

 

 

 

 

 

 

0x95

149

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

value

 

 

 

Meaning

 

 

I/O module is physically

 

 

 

 

 

 

The I/O module process data is:

 

 

 

 

 

 

 

plug fitted*)

 

 

- supplied by the I/O module or

 

 

 

 

 

 

 

 

 

 

 

 

 

supplied to the I/O module

 

 

 

 

 

 

 

not plug fitted

 

 

- set to zero by the controller or

 

 

 

 

 

 

 

 

 

 

 

 

 

ignored by the controller

 

Diagnosis channel x

 

 

 

 

 

 

 

The diagnosis information of the corresponding

 

 

 

 

 

 

 

 

 

 

 

 

channel is

 

 

 

 

 

 

 

 

released

 

 

 

- transmitted to PROFIBUS-DP master

 

 

 

 

 

 

 

locked*)

 

 

 

- not transmitted to PROFIBUS-DP master

 

 

 

 

 

 

 

*) Default setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

 

 

 

 

 

 

 

 

 

Offset

 

Information

 

 

 

 

 

 

 

 

 

 

 

0

 

7

6

5

4

 

3

2

1

0

 

 

 

 

 

 

0

PFC

Plug

0

 

0

Diag

0

0

 

 

 

 

 

 

 

 

 

 

 

 

En0

 

 

 

 

 

 

1

 

7

6

5

4

 

3

2

1

0

 

 

 

 

 

 

1

1

0

0

 

0

0

0

0

 

 

 

 

2

 

15

14

13

12

 

11

9

8

7

 

 

 

 

 

 

reserved

 

 

 

 

 

 

 

 

 

 

 

 

3

 

7

6

5

4

 

3

2

1

0

 

 

 

 

 

 

reserved

 

 

 

 

 

 

 

 

 

 

 

PFC6

 

0

 

Module is mapped in the fieldbus and PFC-PI

 

Plug5

 

1

 

Module is exclusively mapped in the PFC-PI

 

 

0

 

Module is physically not present

 

DiagEn02

 

1

 

Module is physically present (default)

 

 

0

 

Diagnosis locked (default)

 

 

 

 

Italic

 

1

 

Diagnosis release

 

 

 

 

 

 

 

 

Cannot be changed

 

 

 

 

 

WAGO-I/O-SYSTEM 750

D R A F T

PROFIBUS

2001-02-27