Fieldbus coupler / controller |
• 97 |
Fieldbus Controller 750-833 |
|
|
|
3.2.8Configuration and parameterisation of I/O modules
3.2.8.1Digital I/O modules
All binary I/O modules contain 3 bytes of extended parameterisation information, which serve, amongst others, for the identification of the internal bus and the structure of the mapping table. For modules capable of diagnosis the diagnosis message can be suppressed or released channel for channel or module for module. Binary outputs offer the possibility to switch parameterisable substitute values in the case of a master failure.
Note
For simplification only the article numbers are shown as module designation in the table. The module „750-400“ thus corresponds to the module „750-400 2 DI/24 V DC/3.0 ms“
3.2.8.1.1 |
2 DI I/O modules |
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Module |
|
|
|
|
|
|
|
|
|
|
|
Identification |
Identification |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
hex |
dec |
|
|
|
750-400, 750-401, 750-405, 750-406, 750-410, |
|
|
0x10 |
16 |
|||||||||||
|
|
750-411, 750-412 |
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
*750-400, *750-401, *750-405, *750-406, *750-410, |
|
0x00 |
0 |
||||||||||||
|
|
*750-411, *750-412 |
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Parameter |
|
|
|
|
Value |
|
|
|
Meaning |
|
|||||
|
|
I/O module is physically |
|
|
|
|
|
|
|
|
The I/O module process data is: |
||||||
|
|
|
|
|
|
|
|
|
plug fitted*) |
|
|
|
- supplied by the I/O module |
||||
|
|
|
|
|
|
|
|
|
not plug fitted |
|
|
- set to zero by the controller |
|||||
|
|
|
|
|
|
|
|
|
*) Default setting |
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Parameter |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
Offset |
|
Information |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
0 |
|
7 |
6 |
5 |
4 |
|
|
3 |
|
2 |
1 |
0 |
|
|
|
|
|
|
|
0 |
PFC |
Plug |
0 |
|
0 |
|
0 |
0 |
0 |
|
|
|
|
|
|
1 |
|
7 |
6 |
5 |
4 |
|
|
3 |
|
2 |
1 |
0 |
|
|
|
|
|
|
|
0 |
0 |
0 |
0 |
|
0 |
|
0 |
0 |
1 |
|
|
|
|
|
|
2 |
|
7 |
6 |
5 |
4 |
|
|
3 |
|
2 |
1 |
0 |
|
|
|
|
|
|
|
0 |
0 |
0 |
0 |
|
0 |
|
0 |
0 |
0 |
|
|
|
|
PFC6 |
0 |
Module is mapped in the fieldbus and PFC-PI |
Plug5 |
1 |
Module is exclusively mapped in the PFC-PI |
0 |
Module is physically not present |
|
Italic |
1 |
Module is physically present (default) |
|
Cannot be changed |
WAGO-I/O-SYSTEM 750 |
D R A F T |
PROFIBUS |
2001-02-27 |
98 • Fieldbus coupler / controller
Fieldbus Controller 750-833
3.2.8.1.2 |
4 DI I/O modules |
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Module |
|
|
|
|
|
|
|
|
|
|
Identification |
Identification |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
hex |
dec |
|
|
|
750-402, 750-403, 750-408, 750-409, 750-414, |
|
|
0x10 |
16 |
||||||||||
|
|
750-415, 750-423, 750-422, 750-424 |
|
|
|
|
|
|
||||||||
|
|
*750-402, *750-403, *750-408, *750-409, *750-414, |
|
0x00 |
0 |
|||||||||||
|
|
*750-415, *750-423, *750-422, *750-424 |
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Parameter |
|
|
|
|
Value |
|
|
|
Meaning |
|
||||
|
|
I/O module is physically |
|
|
|
|
|
|
The I/O module process data is: |
|||||||
|
|
|
|
|
|
|
|
|
plug fitted*) |
|
|
- supplied by the I/O module |
||||
|
|
|
|
|
|
|
|
|
not plug fitted |
|
|
- set to zero by the controller |
||||
|
|
|
|
|
|
|
|
|
*) Default setting |
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Parameter |
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
Offset |
|
Information |
|
|
|
|
|
|
|
|
|
|
||
|
|
0 |
|
7 |
6 |
|
5 |
4 |
|
3 |
2 |
1 |
0 |
|
|
|
|
|
|
|
0 |
PFC |
|
Plug |
0 |
|
0 |
0 |
0 |
1 |
|
|
|
|
|
1 |
|
7 |
6 |
|
5 |
4 |
|
3 |
2 |
1 |
0 |
|
|
|
|
|
|
|
0 |
0 |
|
0 |
0 |
|
0 |
0 |
0 |
1 |
|
|
|
|
|
2 |
|
7 |
6 |
|
5 |
4 |
|
3 |
2 |
1 |
0 |
|
|
|
|
|
|
|
0 |
0 |
|
0 |
0 |
|
0 |
0 |
0 |
0 |
|
|
|
PFC6 |
0 |
Module is mapped in the fieldbus and PFC-PI |
Plug5 |
1 |
Module is exclusively mapped in the PFC-PI |
0 |
Module is physically not present |
|
Italic |
1 |
Module is physically present (default) |
|
Cannot be changed |
D R A F T |
WAGO-I/O-SYSTEM 750 |
2001-02-27 |
PROFIBUS |
Fieldbus coupler / controller |
• 99 |
Fieldbus Controller 750-833 |
|
|
|
3.2.8.1.32 DI I/O modules with 1 bit diagn. per channel
|
Module |
|
|
|
|
|
|
|
|
|
Identification |
Identification |
||
|
|
|
|
|
|
|
|
|
|
|
|
hex |
dec |
|
|
750-419, 750-425 |
|
|
|
|
|
|
|
0x10 |
16 |
||||
|
*750-419, *750-425 |
|
|
|
|
|
|
|
0x00 |
0 |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Parameter |
|
|
|
Value |
|
|
|
Meaning |
|
||||
|
I/O module is physically |
|
|
|
|
|
|
The I/O module process data is: |
||||||
|
|
|
|
|
|
|
plug fitted*) |
|
|
- supplied by the I/O module |
||||
|
|
|
|
|
|
|
not plug fitted |
|
|
- set to zero by the controller |
||||
|
Diagnosis channel x |
|
|
|
|
|
|
|
The diagnosis information of the corresponding |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
channel is |
|
|
|
|
|
|
|
|
|
released |
|
|
|
- transmitted to PROFIBUS-DP master |
|||
|
|
|
|
|
|
|
locked*) |
|
|
|
- not transmitted to PROFIBUS-DP master |
|||
|
|
|
|
|
|
|
*) Default setting |
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Parameter |
|
|
|
|
|
|
|
|
|
|
|
||
|
Offset |
|
Information |
|
|
|
|
|
|
|
|
|
|
|
|
0 |
|
7 |
6 |
5 |
4 |
|
3 |
2 |
1 |
0 |
|
|
|
|
|
|
0 |
PFC |
Plug |
0 |
|
Diag |
Diag |
0 |
1 |
|
|
|
|
|
|
|
|
|
|
|
En1 |
En0 |
|
|
|
|
|
|
1 |
|
7 |
6 |
5 |
4 |
|
3 |
2 |
1 |
0 |
|
|
|
|
|
|
0 |
0 |
0 |
0 |
|
0 |
1 |
0 |
1 |
|
|
|
|
2 |
|
7 |
6 |
5 |
4 |
|
3 |
2 |
1 |
0 |
|
|
|
|
|
|
0 |
0 |
0 |
0 |
|
0 |
0 |
0 |
0 |
|
|
|
PFC6 |
|
0 |
Module is mapped in the fieldbus and PFC-PI |
|
||||||||||
1Module is exclusively mapped in the PFC-PI
Plug5 |
0 |
Module is physically not present |
DiagEn13 |
1 |
Module is physically present (default) |
|
Diagnosis idle run, short circuit on channel 2 |
|
|
0 |
Locked |
|
1 |
Released |
DiagEn02 |
|
Diagnosis idle run, short circuit on channel 1 |
|
0 |
Locked |
Italic |
1 |
Released |
|
Cannot be changed |
WAGO-I/O-SYSTEM 750 |
D R A F T |
PROFIBUS |
2001-02-27 |
100 • Fieldbus coupler / controller
Fieldbus Controller 750-833
3.2.8.1.42 DO I/O modules
Module |
Identification |
Identification |
|
hex |
dec |
750-501, 750-502, 750-509, 750-512, 750-513, |
0x20 |
32 |
750-514, 750-517 |
|
|
*750-501, *750-502, *750-509, *750-512, *750-513, |
0x00 |
0 |
*750-514, *750-517 |
|
|
|
Parameter |
|
|
|
|
Value |
|
|
|
Meaning |
||||
|
I/O module is physically |
|
|
|
|
|
|
|
|
The I/O module process data is: |
||||
|
|
|
|
|
|
|
plug fitted*) |
|
|
- supplied by the I/O module |
||||
|
|
|
|
|
|
|
not plug fitted |
|
|
- ignored by the controller |
||||
|
Substitute value channel x |
|
|
0*) |
|
|
|
|
If, in the case of a PROFIBUS-DP fault, the |
|||||
|
|
|
|
|
|
|
|
|
|
|
switching of substitute values is enabled by the |
|||
|
|
|
|
|
|
|
1 |
|
|
|
|
|
parameterisation, this data is transmitted to the |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
periphery in the case of a fault. |
|
|
|
|
|
|
|
|
*) Presetting |
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Parameter |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Offset |
Information |
|
|
|
|
|
|
|
|
|
|
|
|
|
0 |
7 |
6 |
5 |
|
4 |
|
3 |
|
2 |
1 |
0 |
|
|
|
|
0 |
PFC |
Plug |
0 |
|
0 |
|
0 |
0 |
0 |
|
|
|
|
1 |
7 |
6 |
5 |
|
4 |
|
3 |
|
2 |
1 |
0 |
|
|
|
|
0 |
0 |
0 |
|
0 |
|
0 |
|
0 |
1 |
0 |
|
|
|
2 |
7 |
6 |
5 |
|
4 |
|
3 |
|
2 |
1 |
0 |
|
|
|
|
0 |
0 |
0 |
|
0 |
|
0 |
|
0 |
SV1 |
SV0 |
|
|
PFC6 |
|
0 |
|
Module is mapped in the fieldbus and PFC-PI |
||||||||||
Plug5 |
|
1 |
|
Module is exclusively mapped in the PFC-PI |
||||||||||
|
0 |
|
Module is physically not present |
|
|
|
||||||||
SV00 |
|
1 |
|
Module is physically present (default) |
||||||||||
|
|
|
Substitute value channel 1 |
|
|
|
||||||||
SV01 |
|
|
|
Substitute channel |
2 |
|
|
|
|
|||||
Italic |
|
|
|
Cannot be changed |
|
|
|
|
||||||
D R A F T |
WAGO-I/O-SYSTEM 750 |
2001-02-27 |
PROFIBUS |
Fieldbus coupler / controller • 101
Fieldbus Controller 750-833
3.2.8.1.52 DO I/O modules with 1 bit diagn. per channel
|
Module |
|
|
|
|
|
|
|
|
|
Identification |
|
Identification |
||
|
|
|
|
|
|
|
|
|
|
|
|
hex |
|
dec |
|
|
750-507, 750-522 |
|
|
|
|
|
|
|
0x20 |
|
32 |
||||
|
*750-507, *750-522 |
|
|
|
|
|
|
|
0x00 |
|
0 |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
Parameter |
|
|
|
Value |
|
|
|
Meaning |
|
|||||
|
I/O module is physically |
|
|
|
|
|
|
The I/O module process data is: |
|||||||
|
|
|
|
|
|
|
plug fitted*) |
|
|
- supplied by the I/O module |
|||||
|
|
|
|
|
|
|
not plug fitted |
|
|
- ignored by the controller |
|
||||
|
Diagnosis channel x |
|
|
|
|
|
|
|
The diagnosis information of the corresponding |
||||||
|
|
|
|
|
|
|
|
|
|
|
|
channel is |
|
||
|
|
|
|
|
|
|
released |
|
|
|
- transmitted to PROFIBUS-DP master |
||||
|
|
|
|
|
|
|
locked*) |
|
|
|
- not transmitted to PROFIBUS-DP master |
||||
|
Substitute value channel x |
|
0*) |
|
|
|
If, in the case of a PROFIBUS-DP fault, the |
||||||||
|
|
|
|
|
|
|
|
|
|
switching of substitute values is enabled by the |
|||||
|
|
|
|
|
|
|
1 |
|
|
|
|
bus controller parameterisation, this data is |
|||
|
|
|
|
|
|
|
|
|
|
|
|
transmitted to the periphery in the case of a |
|||
|
|
|
|
|
|
|
|
|
|
|
|
fault. |
|
||
|
|
|
|
|
|
|
*) Default setting |
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Parameter |
|
|
|
|
|
|
|
|
|
|
|
|
||
|
Offset |
|
Information |
|
|
|
|
|
|
|
|
|
|
|
|
|
0 |
|
7 |
6 |
5 |
4 |
|
3 |
2 |
1 |
0 |
|
|
|
|
|
|
|
0 |
PFC |
Plug |
0 |
|
Diag |
Diag |
0 |
0 |
|
|
|
|
|
|
|
|
|
|
|
|
En1 |
En0 |
|
|
|
|
|
|
|
1 |
|
7 |
6 |
5 |
4 |
|
3 |
2 |
1 |
0 |
|
|
|
|
|
|
|
0 |
0 |
0 |
0 |
|
0 |
0 |
1 |
1 |
|
|
|
|
|
2 |
|
7 |
6 |
5 |
4 |
|
3 |
2 |
1 |
0 |
|
|
|
|
|
|
|
0 |
0 |
0 |
0 |
|
0 |
0 |
SV1 |
SV0 |
|
|
||
PFC6 |
|
0 |
Module is mapped in the fieldbus and PFC-PI |
|
|||||||||||
1Module is exclusively mapped in the PFC-PI
Plug5 |
0 |
Module is physically not present |
DiagEn02 |
1 |
Module is physically present (default) |
|
Diagnosis idle run, overload, short circuit on channel 1 |
|
|
0 |
Locked |
DiagEn13 |
1 |
Released |
|
Diagnosis idle run, overload, short circuit on channel 2 |
|
|
0 |
Locked |
SV00 |
1 |
Released |
|
Substitute value channel 1 |
|
SV01 |
|
Substitute value channel 2 |
Italic |
|
Cannot be changed |
WAGO-I/O-SYSTEM 750 |
D R A F T |
PROFIBUS |
2001-02-27 |